This test room adopts
industrial standard test method, and focuses on factories’
investigation and high educational scientific research. It can
measure the cold capability and electronic data of the air blower
duct, air heater with forced air ventilation, air cooler and it
catered for system development and scientific requirement.
It utilizes the air
enthalpy to measure the testing air-side cold/heat capability and
utilizes the water flowmeter to measure the water-side cold/heat
capability. Test methods are combined with kinds of standard and
requirement (See attachment).
This test room installed
with multifunctional test software and imported international
testing advanced Visual Instruments (Visual Instruments) technology
and configuration, human-machine interface (HMI) to achieve automatic
test. Its graphics and accurate operation ,including course screen,
real time curve, real time report, multi-angular monitoring mode
with real time curve, can satisfy test and application demand by
different careerman
It utilizes graphics and
clear operational interface inclusive flow screen, real time curve,
real time report and multi-purpose real time curve data monitoring
methods that can meet various professional test and application
requirement.
Surface air
cooler: heat transferring coefficient, air resistance, touch
coefficient, water resistance and humidity analysis coefficient
Air blower
duct:cold/heat
capability, air resistance, water resistance
Typical
system data:
²
Air volume
range(m3/h)
210~5000
²
Duct
resistance(Pa)
²
Water flow
resistance(kPa)
²
Cold
capability range(W)
2000~30000
²
Heat
capability range(W)
2500~35000
²
Water flow
volume(m3/h)
0.35~12
Referred Standard:
|
GB/T 19232-2003 |
Air
blower duct unit |
|
JG/T 21-1999 |
Air
cooler with air heater functional test method |
|
ZBJ 72027.3-1989 |
Cabinet air blower duct unit test method |
|
ASHRAE STAND 33-2000 |
Methods of Testing Forced Circulation Air Cooling and
Air
Heating Coils |
|
ARI 440-2005 |
Performance Rating of Room Fan-Coils |
|
ASHRAE 79-2002 |
Methods of Testing for Rating Room Fan-Coil Air Conditioners |
|
ARI 410-98 |
Forced-Circulation Air-Cooling and Air-Heating Coils |